Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15 101
Figure 59. Distributed Bypass System CAN and Pull-Chain Simplified Interface Wiring
UPS 1 UPS 2 UPS 3 UPS 4
CAN
(If Installed)
(If Installed)
Pull Chain
NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physical order.
Figure 60. Distributed Bypass System UPS CAN Wiring without MOBs
Shielded Twisted Pair
Shielded Twisted Pair
Shielded Twisted Pair
UPS 1
CAN Bridge Card J3
UPS 2
CAN Bridge Card J3
UPS 3
CAN Bridge Card J3
(If Installed)
UPS 4
CAN Bridge Card J3
(If Installed)
NOTE External CAN connections between UPSs require shielded twisted-pair wire.
Table 26. CAN Bridge Card Wiring Terminations
From UPS 1 CAN Bridge
Card
From UPS 2 CAN Bridge
Card
To UPS 3 CAN Bridge Card
(If Installed)
To UPS 4 CAN Bridge Card
(If Installed)
J3 8 (L) J3 8 (L) J3 8 (L) J3 8 (L)
J3 9 (H) J3 9 (H) J3 9 (H) J3 9 (H)
J3 10 (Shield) J3 10 (Shield) J3 10 (Shield) J3 10 (Shield)