92 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Figure 55. Normally Closed REPO Switch Wiring
3 (NO)
UPS TB1
REPO
Switch
(NC)
Twisted
Wires
1 (NC)
2 (Return)
4 (Return)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
1
2
Figure 56. Normally Closed and Normally Open REPO Switch Wiring
3 (NO)
UPS TB1
REPO
Switch
(NO)
Twisted
Wires
1 (NC)
2 (Return)
4 (Return)
REPO
Switch
(NC)
NOTE REPO switch rating is 24 Vdc, 1A minimum.
NOTE
T
he REPO switch must be a latching-type switch not tied to any other circuits.
NOTE REPO normally-open and normally-closed return terminals are separated on the terminal board but are electrically in common.
44..1111 IInnssttaalllliinngg OOppttiioonnss,, AAcccceessssoorriieess,, aanndd DDiissttrriibbuutteedd BByyppaassss CCoonnttrrooll WWiirriinngg
To install options, accessories, and distributed bypass control wiring, see
Chapter 5 Installing Options and Accessories