164 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 35 describes the control functions and provides instructions to access and use the command menu
screens.
For detailed information about using the System Controls, see paragraph 7.3 Single UPS Operation.
Figure 105. Typical System Status Screen
MAINTENANCE BYPASS
BYPASS
UPM: OFFLINE
SHUTDOWN:
AVAILABLE:
OFF:
SYSTEM STATUS
CONTROL
S
ESC
FFOREGRAHC :
UPS
Table 34. Typical System Status Messages
Function
Message
UPS Shutdown; Bypass; Online; Online with ESS; Online +VMMS; High Alert
Bypass Off; On; Available
Maintenance Bypass Off; On
Charger Charger Off; Charging
UPM (during startup) DC Starting, Charger Off; DC Starting, Close Battery Breaker; Inverter Starting;
Inverter Syncing; Ready; Online
UPM 1
UPM 4 (if FI-UPM is installed)
Offline; Shutdown, Charger Off; Ready; Ready, Charging; Online, Charger Off; Online,
Charging
Table 35. Command Menu Operation
Function Subfunction
Operation
UPS Control
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command or
proceed to further command screens.
Go to Online Starts the UPS in Online mode or transfers the UPS to Online mode from
Bypass mode.
Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to
Disable when the Energy Saver System mode is enabled.
UPS Operating Instructions