Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15 165
Table 35. Command Menu Operation (Continued)
Function Subfunction
Operation
Enable (Disable) Var Module
Management
Enables or disables the Variable Module Management System mode.
Enable changes to Disable when the Variable Module Management
System mode is enabled.
Start High Alert Starts High Alert mode.
Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Online mode.
Load Off Displays the Load Off screen (see paragraph 7.2.7 Load Off Screen).
Bypass
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command or
proceed to further command screens.
Go to Bypass Starts the UPS in Bypass mode or transfers the UPS to Bypass mode from
Online mode.
Go to Online Starts the UPS in Online mode or transfers the UPS to Online mode from
Bypass mode.
Enable (Disable) Energy Saver Enables or disables Energy Saver System mode. Enable changes to
Disable when the Energy Saver System mode is enabled.
Enable (Disable) Var Module
Management
Enables or disables the Variable Module Management System mode.
Enable changes to Disable when the Variable Module Management
System mode is enabled.
Start High Alert Starts High Alert mode.
Load Off Displays the Load Off screen (see paragraph 7.2.7 Load Off Screen).
Charger
Control
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off.
UPM Control
Commands
Use the up or down arrow pushbutton to highlight the command function
desired, then press the SELECT pushbutton to execute the command.
UPM On Turns the UPM on without transferring the load to Online mode. The Load
is on bypass.
UPM Off Transfers the load to bypass and turns the UPM off.
UPM Go to Online Turns the UPM on and transfers the load to Online mode.
Charger On Turns the battery charger on.
Charger Off Turns the battery charger off.
NOTE The Energy Saver System and Variable Module Management System mode commands are displayed only if enabled at the
factory or by an Eaton Customer Service Engineer.
NOTE Variable Module Management System and Energy Saver System modes are mutually exclusive.