104 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 28. Pull-Chain Wiring Terminations with MOBs
From
To Function
UPS 1 CAN Bridge Card J3–1 (Alarm)
MOB 1 Aux 1 NC
MOB Open Alarm
UPS 1 CAN Bridge Card J3–2 (Alarm
Return)
MOB 1 Aux 1 Com
UPS 1 TB2–1 (Pull Chain)
MOB 1 Aux 2 NO Pull Chain
UPS 2 TB2–2 (Pull Chain Common) UPS 2 TB2–2 (Pull Chain Common)
Pull Chain Common
UPS 2 CAN Bridge Card J3–1 (Alarm)
MOB 2 Aux 1 NC
MOB Open Alarm
UPS 2 CAN Bridge Card J3–2 (Alarm
Return)
MOB 2 Aux 1 Com
UPS 2 TB2–1 (Pull Chain) MOB 2 Aux 2 NO Pull Chain
UPS 2 TB2–2 (Pull Chain Common) UPS 3 TB2–2 (Pull Chain Common) Pull Chain Common
UPS 3 CAN Bridge Card J3–1 (Alarm)
MOB 3 Aux 1 NC
MOB Open Alarm
UPS 3 CAN Bridge Card J3–2 (Alarm
Return)
MOB 3 Aux 1 Com
UPS 3 TB2–1 (Pull Chain) MOB 3 Aux 2 NO Pull Chain
UPS 3 TB2–2 (Pull Chain Common) UPS 4 TB2–2 (Pull Chain Common) Pull Chain Common
UPS 4 CAN Bridge Card J3–1 (Alarm)
MOB 4 Aux 1 NC
MOB Open Alarm
UPS 4 CAN Bridge Card J3–2 (Alarm
Return)
MOB 4 Aux 1 Com
UPS 4 TB2–1 (Pull Chain) MOB 4 Aux 2 NO
Pull Chain
MOB 1 Aux 2 Com MOB 2 Aux 2 Com
Pull Chain MOB CommonMOB 2 Aux 2 Com MOB 3 Aux 2 Com
MOB 3 Aux 2 Com MOB 4 Aux 2 Com
55..44 IInnssttaalllliinngg aann OOppttiioonnaall RReemmoottee MMoonniittoorr PPaanneell IIII
To install RMP II wiring:
1. Verify the UPS system is turned off and all power sources are removed. See
Chapter 7 UPS Operating Instructions for shutdown instructions.
2. Perform the procedure listed in paragraph Figure 60.
NOTE If mounting to a hollow wall, secure the enclosure to a wood or metal stud within the
wall. Do not use hollow wall anchors.
3. Securely mount the RMP II at the desired location. See Figure 68 for mounting hole locations.
Installing Options and Accessories