160 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 33. Display Menu Operation (Continued)
Function Subfunction
Operation
Output Current UPS
Output Current UPM
The Output Current screen displays a real time bar graph of the output current
of the UPS. The graph shows the current for each phase.
Output Power UPM The Output Power screen displays the power in kW and kVA for each UPM.
System Level 0 Setup Function Selection This screen can be used to set the screen contrast, show the firmware
versions installed, identify the unit type, change the display language, set up
Energy Saver functions, set up Advanced Power Management functions, and
enter a password to access Level 1 functions. Press the SETUP pushbutton on
the main menu bar to display the System Setup Level 0 Screen. No password
is necessary to access Level 0 functions. Use the up or down arrow
pushbutton to highlight the setup function screen desired, then press the
SELECT pushbutton to display the function screen.
Contrast Adjust Select CONTRAST from the System Setup Level 0 menu to display the
Contrast Adjust screen. Use the left or right arrow pushbutton to adjust the
contrast for the LCD. When the contrast adjustment is complete, press the
SAVE pushbutton. Once the setting is saved, the System Setup screen
displays. To return to the System Setup screen without saving the setting,
press the ESC pushbutton.
Firmware Versions The Versions screen provides the firmware version numbers installed on the
UPS. Select VERSIONS from the System Setup Level 0 menu to display the
Versions screen. To scroll through the firmware types, press the up or down
arrow pushbutton on the menu bar. To return to the System Setup screen,
press the ESC pushbutton.
Identification The Unit Type screen provides the model, CTO, and serial numbers of the UPS
unit. Select UNIT TYPE from the System Setup Level 0 menu to display the
Unit Type screen. To return to the System Setup screen, press the ESC
pushbutton.
Language The Language Setup screen allows the display menu language to be set.
Select LANGUAGE SETUP from the System Setup Level 0 menu to display
the Language Setup screen. Use the up or down arrow pushbutton to highlight
the desired language, then press the SELECT pushbutton. To return to the
System Setup screen, press the ESC pushbutton.
Energy Saver System The Energy Saver System Setup screen allows the Energy Saver function to be
configured. Select ENERGY SAVER SYSTEM SETUP from the System Setup
Level 0 menu to display the Energy Saver System Setup screen. Use the up or
down arrow pushbutton to highlight the desired function, then press the
SELECT pushbutton. To return to the System Setup screen, press the ESC
pushbutton.
Storm Detection Counter The Storm Detection Counter screen sets the number of power line
disturbances that can occur before the UPS locks into Online mode. Select
STORM DETECTION COUNTER from the Energy Saver System Setup screen
to display the Storm Detection Counter screen. Use the up or down arrow
pushbutton to set the counter. Press SAVE or ABORT. Once the action is
completed, the Energy Saver System Setup screen is displayed.
Storm Detection Timer The Storm Detection Timer screen sets the length of time that power line
disturbances are monitored. The time can be set in 10 minute increments from
0 to 990 minutes. Select STORM DETECTION TIMER from the Energy Saver
UPS Operating Instructions