172 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
NOTE 1 The Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer.
NOTE 2 The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4. On the Bypass Control Command screen, select DISABLE VAR MODULE MANAGEMENT.
5. Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode in approximately ten
seconds.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
77..33..1144 SSttaarrtt VVaarriiaabbllee MMoodduullee MMaannaaggeemmeenntt SSyysstteemm HHiigghh AAlleerrtt MMooddee ffrroomm BByyppaassss CCoommmmaanndd MMeennuu
To start High Alert mode:
NOTE 1 The High Alert mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE 2 The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4. On the Bypass Control Command screen, select START HIGH ALERT.
5. Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS starts High Alert mode with the UPMs online supplying the critical load. After
one hour the UPS transfers to Variable Module Management System mode.
The Online status indicator is illuminated. The UPS status indicates HIGH ALERT. The UPM status
indicates ONLINE. The power module is on.
77..33..1155 SSttaarrttiinngg tthhee UUPPMMss
To start the power module without transferring the critical load to Online mode:
1. Unfasten the front door latch and swing the door open (see Figure 22).
2. If the UPS contains input breaker CB1, verify that input breaker CB1 is open.
3. Close the UPS input feeder circuit breaker.
4. Close the UPS Bypass input feeder circuit breaker.
5. If the UPS contains input breaker CB1, close input breaker CB1.
UPS Operating Instructions