182 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the UPS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4. On the UPS Control Command screen, select ENABLE ENERGY SAVER.
5. Press the SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE WITH ESS. The UPM status
indicates ONLINE.
If the battery is not charging, the power module is off.
77..44..33 DDiissaabbllee EEnneerrggyy SSaavveerr SSyysstteemm MMooddee ffrroomm tthhee UUPPSS CCoommmmaanndd MMeennuu
To disable Energy Saver System mode:
NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2 The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the UPS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4. On the UPS Control Command screen, select DISABLE ENERGY SAVER.
5. Press the SELECT pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
77..44..44 SSttaarrtt EEnneerrggyy SSaavveerr SSyysstteemm HHiigghh AAlleerrtt MMooddee ffrroomm tthhee UUPPSS CCoommmmaanndd MMeennuu
To start High Alert mode:
NOTE 1 The High Alert mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE 2 The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the UPS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4. On the UPS Control Command screen, select START HIGH ALERT.
UPS Operating Instructions