Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15 185
14. Press the SELECT pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source in Bypass mode from all UPSs.
The BYPASS status indicator is illuminated. The Bypass status indicates ON. The UPM status indicates
SHUTDOWN, CLOSE BATTERY.
77..44..99 EEnnaabbllee EEnneerrggyy SSaavveerr SSyysstteemm MMooddee ffrroomm tthhee BByyppaassss CCoommmmaanndd MMeennuu
To enable Energy Saver System mode:
NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2 The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable Module
Management System mode commands will not be displayed.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4. On the Bypass Control Command screen, select ENABLE ENERGY SAVER.
5. Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE WITH ESS. The UPM status
indicates ONLINE. If the battery is not charging, the power module is off.
77..44..1100 DDiissaabbllee EEnneerrggyy SSaavveerr SSyysstteemm MMooddee ffrroomm tthhee BByyppaassss CCoommmmaanndd MMeennuu
To disable Energy Saver System mode:
NOTE 1 The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2 The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
1. Press the CONTROLS pushbutton on the main menu bar. The System Status screen is displayed.
2. On the System Status screen, select the BYPASS command.
3. Press the CONTROLS pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4. . On the Bypass Control Command screen, select DISABLE ENERGY SAVER.
5. Press the SELECT pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates ONLINE. The UPM status indicates
ONLINE.
77..44..1111 SSttaarrtt EEnneerrggyy SSaavveerr SSyysstteemm HHiigghh AAlleerrtt MMooddee ffrroomm tthhee BByyppaassss CCoommmmaanndd MMeennuu
To start High Alert mode:
UPS Operating Instructions