EasyManua.ls Logo

Eaton Power Xpert 9395 - Page 89

Eaton Power Xpert 9395
269 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
66 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Figure 34. ISBM Section Output Power Terminal Detail
NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised
barrel portion facing the back of the cabinet. Install the second lug with the raised barrel portion facing the front of the cabinet.
AC Output
from UPMs
UPM 1 Cable 1G4 & 1G5 Orange
Phase A (E9A)
UPM 2 Cable 2G4 & 2G5 Orange
UPM 3 Cable 3G4 & 3G5 Orange
UPM 1 Cable 1G4 & 1G5 Brown
UPM 2 Cable 2G4 & 2G5 Brown
UPM 3 Cable 3G4 & 3G5 Brown
UPM 1 Cable 1G4 & 1G5 Yellow
UPM 2 Cable 2G4 & 2G5 Yellow
UPM 3 Cable 3G4 & 3G5 Yellow
UPM 1 Cable 1G4 & 1G5 Gray
UPM 2 Cable 2G4 & 2G5 Gray
UPM 3 Cable 3G4 & 3G5 Gray
Phase B (E10A)
Phase C (E11A)
Neutral from
UPMs (E12A)
UPM 4 Cable 4G4 & 4G5 Gray
UPM 4 Cable 4G4 & 4G5 Yellow
UPM 4 Cable 4G4 & 4G5 Brown
UPM 4 Cable 4G4 & 4G5 Orange
NOTE Cables 3G4 & 3G5 and 4G4 & 4G5 are not used with Two UPM systems.