ADDITIONAL UPS FEATURES
Eaton 5130 Rack/Tower UPS (1000–3000 VA) User's Guide S 164201730 Rev 4
www.eaton.com/powerquality
44
Table 6. Voltage Threshold Options
Low-Voltage Model Function Factory Setting Other Available Settings
High threshold for transfer to battery
151 Vac ±3% 141–153 Vac
Low threshold for transfer to battery
89 Vac ±3% 89–94 Vac
Fader activation threshold
132 Vac ±3% 127–138 Vac
Booster activation threshold
102 Vac ±3% 92–108 Vac
Maximum input-voltage range
Disabled Enabled
1
High-Voltage Model Function Factory Setting Other Available Settings
High threshold for transfer to battery
294 Vac 271–294 Vac
Low threshold for transfer to battery
160 Vac 160–180 Vac
Fader activation threshold
265 Vac 244–265 Vac
Booster activation threshold
184 Vac 184–207 Vac
Maximum input-voltage range
Disabled Enabled
2
1
Low threshold for transfer to battery is 70V.
2
Low threshold for transfer to battery is 150V.
PW5130G3000-XL2U Function Factory Setting Other Available Settings
High threshold for transfer to battery
263 Vac —
Low threshold for transfer to battery
160 Vac —
Fader activation threshold
229 Vac —
Booster activation threshold
177 Vac —
Maximum input-voltage range
Disabled Enabled
2
2
Low threshold for transfer to battery is 150V.
Table 7. UPS Sensitivity Options
Function
Factory Setting Other Available Settings
UPS-sensitivity level
Normal High or low