Chapter 7 Specifications
Filter
Transformer
“AVR” Charger Inverter
Battery
Figure 30. Block Diagram
Table 10. Low-Voltage Model Specifications
Model Number
Power Levels
(Rated at
Nominal Inputs)
AC Input Output on Battery Power
Nominal
Voltage
Voltage
Range
1
Frequency
Range
2
Voltage
3
Frequency
PW5130L1000-XL2U 1000 VA, 1000W
120V 89–151V
47–70 Hz (50 Hz
system),
56.5–70 Hz (60 Hz
system)
120V
(+6/-10%)
50/60 Hz
±0.1%
PW5130L1500-XL2U 1500 VA, 1400W
PW5130L2200-XL2U 2200 VA, 1920W
PW5130L3000-XL2U
2880 VA, 2700W
PW5130L3000-XL3U
1
The high and low thresholds can be adjusted using the UPS Configuration tool (see page 43).
2
Up to 40 Hz in low-sensitivity mode (programmable using the UPS Configuration tool).
3
Adjustable to 100V (10% derating of output power) 120/127V.