21
9.0 Specifications
Powerware reserves the right to change specifications without prior notice.
This section provides the following specifications for the Powerware 9120 6kVA model:
• Electrical input and output
• Environmental and safety
• Weights and dimensions
• Battery
Table 4. Electrical Input
240V Models
Nominal Voltage 240V default; 208, 220, 230, 240V selectable
Voltage Range 184-276V for 208, 220, 230, 240V nominal
Low line is 120V at 25% load, 140V at 50% load, 160V at
75% load, 184V at 100% load without battery discharge
Nominal Frequency 50/60 Hz, ±5% user-selectable
Noise Filtering MOVs and line filter for normal and common mode noise
Connections Hardwired Input 10mm
2
max. cable, separate bypass source,
terminals standard
Input Power Factor 0.97
Max. Input Current 30A
Table 5. Electrical Output
240V Models
Power Levels 6000VA, 4200W
(rated at nominal inputs)
Regulation Nominal output voltage ±2%
(Normal mode)
Overload Capacity 100 - 125% 1 minute
125 - 150% 10 seconds
Voltage Waveform Normal mode: Sine wave; <5% THD with full PFC and
nonlinear load
Output Connections Hardwired 10mm
2
cable maximum