EasyManua.ls Logo

Eaton Powerware 9155 - Page 27

Eaton Powerware 9155
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INPUT ISOLATION TRANSFORMER INSTALLATION
EATON Powerware
®
9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev F www.powerware.com
21
17. Hardwire the input terminations (TB1-1 through TB1-3) for the input isolation
transformer.
See Table 2 for specifications and Figure 10 for a detailed view of the input
isolation transformer terminal block.
18. Punch a hole in the bottom of the MBM/PDM using a Greenlee punch or similar
device for wiring access.
Insert the supplied nylon bushing inside the wiring access hole.
19. Continue to the following chapter, “UPS-Mounted Bypass Switch Installation,” t o
complete the installation.

Table of Contents

Other manuals for Eaton Powerware 9155

Related product manuals