UPS WITH BYPASS ELECTRICAL INSTALLATION
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
23
NOTE In the UPS or LINE position, AC input power is still connected to the input terminals
inside the UPS.
Table 3. Bypass Switch Positions
Switch Position Description
LINE Connects the load directly to AC input pow er and disconnects UPS output. AC input power is
still connected to the UPS input.
OFF Disconnects the load from the UPS output power and AC input power, as well as AC input
power to the UPS input.
UPS Connects the UPS output to the load.
SERVICE Like the LINE position, SERVICE connects the load directly to AC input power and disconnects
UPS output. However, because SERVICE also disconnects AC input from the U PS, this is
the appropriate position for UPS maintenance or repair.
To disconnect AC input power during maintenance or service, turn the
bypass switch to the SERVICE position. For MBB switches, you must
press the red button beside the switch before you can change the
switch position.
Table 4 shows the bypass switch models available for the Powerware
9170
+
UPS.
Table 4. Bypass Switch Specifications
Bypass Switch Models See Figure 14
B
B
M
M
B
B
Rating,
C
o
n
t
i
n
u
o
u
s
Height Width Depth Mounting Centers
Weight
BBM MBB
C
o
n
t
i
n
u
o
u
s
(A) (B) (C) (D) (E)
BPE12BBM1A BPE12MBB1A 40A/300 Vac
(CSA)
50A/300 Vac
(UL,TÜV)
53.4 cm
(21.0)
35.6 cm
(14.0)
17.2 cm
(6.8)
28.0 cm
(11.0)
50.8 cm
(20.0)
12.3 kg
(27 lb)
BPE14BBM1A BPE14MBB1A 80A/300 Vac 53.4 cm
(21.0)
35.6 cm
(14.0)
17.2 cm
(6.8)
28.0 cm
(11.0)
50.8 cm
(20.0)
14.1 kg
(31 lb)
BPE20BBM1A BPE20MBB1A 125A/300 Vac 53.4 cm
(21.0)
35.6 cm
(14.0)
17.2 cm
(6.8)
28.0 cm
(11.0)
50.8 cm
(20.0)
15.9 kg
(35 lb)