UPS STARTUP
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
69
Figure 49. Inserting the Modules
4. If you installed an optional battery cabinet, repeat Steps 1 and 2 to
install the battery modules.
5. Reinstall the front cover(s).
6. Continue to the following section, “Startup for Plug-Receptacle
Units” if your cabinet has a power cord already attached. If you
hardwired the UPS, skip to “Startup for Hardwired Units” on
page 72.
Startup f or Plug-Receptacle Units
To start a plug-receptacle unit:
1. Plug the power cable of the unit into an approved, functional power
outlet.
2. If external battery cabinets are installed, check the cable
connections between the UPS and external battery cabinets.
Close the DC disconnect switch button on the back of each external
battery cabinet. Insert the switch key supplied with the cabinet into
the button and turn clockwise 1/2-turn. Pull the button out to close
the switch. Turn the key back counter-clockwise, and remove the
key.