EasyManua.ls Logo

Eaton Powerware 9170+ - Neutral-to-Ground Bonding for Isolated Output

Eaton Powerware 9170+
126 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ISOLATED OUTPUT WIRING DIAGRAMS
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
54
100, 110,
115, or 120
X2
50 or 60 Hz
100/200, 110/220, 115/230, or 120/240V Out
with Isolated Output Option
Menu424setto200, 220, 230, or 240, as required.
X1 X3
XX
N-G Bond
L2N
X
L1
200, 220, 230, or 240
100, 110,
115, or 120
X0
Figure 36. Isolated Outputs Single-Phase Voltages
X2
50 or 60 Hz
120/208 or 127/220V Out
with Isolated Output Option
Menu424setto208or220, as required.
X1 X3
XX
N-G Bond
L2N
X
L1
208 or 220
120 or 127
X0
88 or 93
Figure 37. Isolated Outputs Derived Three-Phase Voltages
Neutral-to-Ground Bonding for Isolated Output
As required under safety regulations issued by various regulatory
agencies, the UPS cabinet must have a ground-bond connection for t he
neutral terminal of an isolated-output system. In such a system, the
customer must make the neutral-to-ground (also referred to as N-G or
neutral-to-earth) connection after selecting the desired output
configuration.
In isolated-output systems, connect the neutral-to-ground (neutral-to-earth)
wire to t he proper terminal before making any other connections to the UPS.A
green and yellow neutral-to-ground bonding wire is supplied, with one
end connected to the ground (earth) UPS terminal as shown in
Figure 38. The other end of the wire (as shown by * in Figure 38) must
be attached to the proper output neutral terminal, as specified in
Figure 36 and Figure 37.

Table of Contents

Related product manuals