UPS WITH BYPASS ELECTRICAL INSTALLATION
EATON Powerware
®
9170
+
UPS (3–18 kVA) User’s Guide S 164201393 Rev C www.powerware.com
27
6. Install the conduit adapters. AC input and AC output conductors
must be run through separate conduits. UPS output circuits must
be installed in dedicated conduit systems and not shared with other
electrical circuits.
Figure 16 shows input and output wiring terminals inside the
Powerware 9170
+
UPS cabinet.
321
+DC X1X2
N
-DC
N
-DC
X2
+DC X1
Backplane Board
Terminating
Studs
X3
Figure 16. UPS Input and Output Terminals