EasyManua.ls Logo

Eaton PowerXL DC1 20 Series - Dc1-12

Eaton PowerXL DC1 20 Series
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Installation
3.7 Block diagrams
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 109
3.7.2 DC1-12…
Mains voltage U
LN
: single-phase, 200 (-10 %) - 240 (+10 %) V, 50/60 Hz
Motor voltage U
2
: 3-phase, U
2
= U
LN
, 0 - 50/60 Hz (max. 500 Hz)
Size: FS1, FS2 and FS3 with IP20 degree of protection
Figure 64: Block diagram DC1-12…
Variable frequency drive with
single-phase
supply
system voltage and three-
phase motor connection
DC+
BR
DC-
3 AC 230 V
WVU
M
3 ~
L1/L
EMC
L2/N
1 AC 200 - 240 V
50/60 Hz
PES
2
DI1
FWD
+24 V
3
DI2
REV
4
DI3
(AI2)
f-fix1
5
+10 V Out
< 10 mA
+10 V
6
AI1
(DI4)
REF
7
0 V
1
+24 V Out
< 100 mA
8
AO
(DO)
0...+10 V, < 20 mA
f-Out
+
9
0 V
10 11
RUN
6 A, 250 V AC
5 A, 30 V DC
RS485
CPU
0...+10 V
Modbus RTU
CANopen
OP-Bus
X1
FS2,
FS3
R
B
Devices with a frame size of FS2 or FS3 allow for DC link coupling
(DC+, DC-) and connecting brake resistors (DC+, BR).
Brake resistor DX-BR3-100 can be inserted underneath the heat sink into
the enclosure and electronically protected against overloads (P-34 = 1).
DC1-12xxxN…: without radio interference suppression filter
DC1-12xxxF…: with built-in radio interference suppression filter

Table of Contents