6 Technical Data
6.2 Specific rated operational data
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 153
DC1-32… device series
Continue
Size Symbol Unit 011 018 024 030 046
Rated operational current I
e
A 10.5 18 24 30 46
Overload current for 60 s every 600 s i
l
A 15.75 27 36 45 69
Overload current for 2.5 s every 600 s i
l
A 18.38 31.5 42 52.5 80.5
Apparent power at rated operation
230 V
SkVA4.18 7.17 9.55 11.94 18.30
Apparent power at rated operation
240 V
SkVA
4.36 7.48 9.96 12.46 19.10
Assigned motor power
at 230 V, 50 Hz P kW 2.2 4 5.5 7.5 11
at 220 - 240 V, 60 Hz P HP 3 5 7.5 10 15
Power side (primary side):
Number of phases 3 3 3 3 3
Rated operating voltage U
LN
V 200 - 10 % - 264 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current) I
LN
A 12.1 20.9 26.4 33.3 50.1
Minimum braking resistance R
B
Ω 50 25 20 15 10
Switching frequency (pulse frequency)
Default Setting f
PWM
kHz 8 8 8 8 8
Setting range f
PWM
kHz 4 -32 4 -24 4 -24 4 -24 4 -24
Voltage Boost (U
Boost
/U
LN
)
Default Setting % 2.5 2 2 1.5 1.5
Max Value %
20 15 15 10 10
Maximum leakage current to earth
(touch current), at U
LN
: 240 V, without
motor
I
Touch
mA 7.2 6.8 6.8 6.9 6.9
Efficiency η 0.96 0.96 0.97 0.97 0.96
Heat dissipation
At I
e
(150 %) P
V
W 90.2 160 223 304 446
During no-load running, standby
(locked, without fan)
P
V
W 4.51 5.16 5.16 7.54 7.54
Fan
✓
1)
✓
1)
✓
1)
✓ ✓
Size FS2 FS3 FS3 FS4 FS4
1) Not with IP66 degree of protection