6 Technical Data
6.2 Specific rated operational data
152 DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com
6.2.3 DC1-32… device series
Size Symbol Unit 2D3 4D3 7D0NN 7D0NB
7D0FB
Rated operational current I
e
A 2.3 4.3 7 7
Overload current for 60 s every 600 s i
l
A 3.45 6.45 10.5 10.5
Overload current for 2.5 s every 600 s i
l
A 4.03 7.53 12.25 12.25
Apparent power at rated operation
230 V
SkVA0.92 1.71 2.79 2.79
Apparent power at rated operation
240 V
SkVA
0.96 1.79 2.91 2.91
Assigned motor power
at 230 V, 50 Hz P kW 0.37 0.75 1.5 1.5
at 220 - 240 V, 60 Hz P HP
0.5 1 2 2
Power side (primary side):
Number of phases 3 3 3 3
Rated operating voltage U
LN
V 200 - 10 % - 240 + 10 %, 50/60 Hz
180 - 264 ±0 %, 48 - 62 Hz ±0 %
Input current (phase current) I
LN
A 3.4 5.6 9.5 8.9
Minimum braking resistance R
B
Ω – – – 100
Switching frequency (pulse frequency)
Default Setting f
PWM
kHz 8 8 8 8
Setting range f
PWM
kHz 4 -32 4 -32 4 -32 4 -32
Voltage Boost (U
Boost
/U
LN
)
Default Setting % 3 3 3 2.5
Max Value % 25 25 25 20
Maximum leakage current to earth
(touch current), at U
LN
: 240 V, without
motor
I
Touch
mA 7.5 7.5 7.5 7.2
Efficiency η
0.96 0.95 0.96 0.96
Heat dissipation
At I
e
(150 %) P
V
W 14.8 39.75 61.5 61.5
During no-load running, standby
(locked, without fan)
P
V
W 3.07 3.07 3.07 4.51
Fan
– ✓
1)
✓
1)
✓
1)
Size FS1 FS1 FS1 FS2
1) Not with IP66 degree of protection