3 Installation
3.5 EMC installat ion
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 75
3.5.4 Screen earth kit
Cables that are not screened work like antennas (sending, receiving).
The effectiveness of the cable screen depends on a good screen connection
and a low screen impedance.
For a proper EMC connection, cables emitting interference (e.g.
motor cables) and susceptible cables (analog signal and
measured values) must be screened and laid separately from
each other.
Use only screens with tinned or nickel-plated copper braiding.
Screens made of steel braids or metal conduits are either not
suitable or suitable only to a limited extent (depending on the
EMC environment).
Control and signal lines (analog, digital) should always be
grounded on one end, in the immediate vicinity of the supply
voltage source (PES).