6 Technical Data
6.2 Specific rated operational data
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 155
DC1-34…device series
Continue
Size Symbol Unit 014 018 024 030 039 046
Rated operational current I
e
A 14 18 24 30 39 46
Overload current for 60 s every 600 s i
l
A 21 27 36 45 58.5 69
Overload current for 3.75 s every 600 s i
l
A 24.5 31.5 42 52.5 68.25 80.5
Apparent power at rated operation
400 V
SkVA9.67 12.47 16.63 20.76 26.99 31.83
Apparent power at rated operation
480 V
SkVA
11.64 14.96 19.95 24.91 32.39 38.20
Assigned motor power
at 400 V, 50 Hz P kW 5.5 7.5 11 15 18.5 22
at 460 V, 60 Hz P HP 7.5 10 15 20 25 30
Power side (primary side):
Number of phases 3 3 3 3 3 3
Rated operating voltage U
LN
V 380 V - 10 % - 480 V + 10 %, 50/60 Hz
342 - 528 V ±0 %, 48 - 62 Hz ±0 %
Input current (phase current) I
LN
A 17.2 21.2 27.5 34.2 44.1 51.9
Minimum braking resistance R
B
Ω 100 80 50 30 22 22
Switching frequency (pulse frequency)
Default Setting f
PWM
kHz 8 8 8 8 8 8
Setting range f
PWM
kHz 4 - 24 4 - 24 4 - 24 4 - 24 4 - 24 4 - 24
Voltage Boost (U
Boost
/U
LN
)
Default Setting % 2 2 2 2 1.5 1.5
Max Value %
15 15 15 10 10 10
Maximum leakage current to earth
(touch current), at U
LN
: 400 V, without
motor
I
Touch
mA 12.7 12.7 12.7 12.9 12.9 12.9
Efficiency η 0.96 0.97 0.97 0.97 0.97 0.96
Heat dissipation
At I
e
(150 %) P
V
W 223 304 446 607 728 801
During no-load running, standby
(locked, without fan)
P
V
W 6.42 6.42 6.52 14.6 14.6 14.6
Fan
✓
1)
✓
1)
✓
1)
✓ ✓ ✓
Size FS3 FS3 FS3 FS4 FS4 FS4
1) Not with IP66 degree of protection