7 Accessories
7.1 Device-specific accessories
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 183
Table 48: Specific technical data DXC-EXT-IO…
Technical data Unit Value
Input voltage
DXC-EXT-IO110 V 100 - 10 % - 120 + 10 %, 50/60 Hz
(90 - 132 ± 0 %, 48 - 62 Hz ± 0 Hz)
DXC-EXT-IO230 V 200 - 10 % - 240 + 10 %, 50/60 Hz
(180 - 264 ± 0 %, 48 - 62 Hz ± 0 Hz)
High signal
DXC-EXT-IO110 V 80 - 250 , R
i
68 kΩ
DXC-EXT-IO230 V 80 - 250 , R
i
68 kΩ
Degree of protection (without
the connection pins being
covered by the DC1’s control
signal terminal block)
IP00
For detailed instructions on how to install the expansion
modules, please refer to instruction leaflet IL04012016Z.
NOTICE
Internal relay K1 is looped with the expansion module, meaning
it can only conduct a lower current ( 1A).
DANGER
Dangerous voltage!
Expansion modules DXC-EXT-IO110 and DXC-EXT-IO230 must
not be placed into operation until all mounting and installation
work has been completed. Any other use will be considered to
be an inappropriate use.

Table of Contents