7 Accessories
7.1 Device-specific accessories
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 185
Figure 93: Block diagram DXC-EXT-2RO
Parameter Definition
The K1 relay output’s function can be configured using parameter P-18
(default setting = 1: RUN). Meanwhile, the new K2 relay output’s function
can be configured using parameter P-25 (default setting = Analog output
AO1).
Parameter P-25 must be set to a value between 0 and 7 in order
for the output to function as a digital output.
If the parameter is set to a value greater than 7, relay output K2
will not work properly.
2
DI1
3
DI2
4
DI3
1
5
+10 V
< 20 mA
6 7
0 V
8 9 10 11
1DC1 2 3 4 5 6 8 9 10 11
P-18 = 1
RUN
P-25
7
AI
0 ... +10 V
+24 V
< 100 mA
f-Soll
K2 K1
250 V AC
220 V DC
≦ 1 A
4.7 kΩ