EasyManua.ls Logo

Eaton PowerXL DC1 20 Series - Page 85

Eaton PowerXL DC1 20 Series
197 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3 Installation
3.6 Electrical Installation
DC1…20… and DC1…OE1 Variable Frequency Drives 02/20 MN040059EN www.eaton.com 81
3.6.1.1 Terminals in power section for units with IP20 degree of protection
Table 6: Terminals (IP20)
Size
Connection terminals Description
FS1 Connection with single-phase supply voltage:
DC1-1D… (115 V)
DC1-12… (230 V)
Note:
Connection to terminal L3 not permissible!
Connection with three-phase supply voltage:
DC1-32… (230 V)
DC1-34… (400 V, 480 V)
Motor connection for three-phase motors:
DC1-1D… (230 V)
DC1-12… (230 V)
DC1-32… (230 V)
DC1-34… (400 V, 460 V)
FS2, FS3
Connection with single-phase supply voltage (115 V, 230 V):
DC1-1D (115 V)
DC1-12 (230 V)
Note:
Connection to terminal L3 not permissible!
DC-: Negative DC link connection if using DC link coupling.
The terminal’s plastic cover can be removed if necessary.
Connection with three-phase supply voltage:
DC1-32… (230 V)
DC1-34… (400 V, 480 V)
Note:
DC-: Negative DC link connection if using DC link coupling.
The terminal’s plastic cover can be removed if necessary.
Motor connection for three-phase motors:
DC1-1D… (230 V)
DC1-12… (230 V)
DC1-32… (230 V)
DC1-34… (400 V, 460 V)
Note:
DC+: Positive DC link connection if using DC link coupling or braking
chopper.
The terminal’s plastic cover can be removed if necessary.
BR: Terminal for brake resistor (braking chopper output).
The terminal’s plastic cover can be removed if necessary.
L1/L L2/N L3
LN
PE
L1/L L2/N L3
L1 L2
PE
L3
UVW
PES
M
3
DC- L1/L L2/N L3
LN
PE
DC- L1/L L2/N L3
L1 L2
PE
L3
PES
DC+ BR U V W
R
B
M
3

Table of Contents