57
Appendix A—Technical data and specifi cations
POWERXL SERIES VFD MN040002EN—February 2018 www.eaton.com
Attribute Description Specification
Ambient conditions,
continued
Altitude 100% load capacity (no derating) up to 3280 ft (1000 m); 1% derating for each 328 ft (100 m) above
3280 ft (1000 m); max. 9842 ft (3000 m) (2000 m for corner grounded earth main systems)
For 600 V product, maximum altitude is 2000 m regardless of main system
Vibration:
EN 61800-5-1
• EN 60068-2-6
5–150 Hz
Displacement amplitude: 1 mm (peak) at 5 Hz to 15.8 Hz (FR0FR6)
Maximum acceleration amplitude: 1g at 15.8 Hz to 150 Hz (FR0–FR6)
Shock:
ISTA 1 A
• EN 60068-2-27
Storage and shipping: maximum 15 g, 11 ms (in package)
Overvoltage Overvoltage Category III
Pollution degree Pollution Degree 2
Enclosure class FR0: Open Type /IP20
FR1–FR6: IP21/Type 1 standard in entire kW/hp range
IP54/Type 12 option
Note: Keypad or keypad hole plug required to be mounted in drive for IP54/Type 12 rating
Immunity Fulfills IEC/EN 61800-3 (2004) + A1 (2012), first and second environment
MTBF FR0:150,000 hours
FR1:165,457 hours
FR2:134,833 hours
FR3:102,515 hours
FR4:121,567 hours
FR5:108,189 hours
FR6:100,000 hours
Noise FR0:51.7 dB
FR1:51.2 dB
FR2:58.6 dB
FR3:61.0 dB
FR4:68.0 dB
FR5:69.1 dB
FR6:73.2dB
Standards Safety UL508C, CSA C22.2 No. 274-13 / CSA C22.2 No. 274-17 and EN61800-5-1
EMC IEC/EN 61800-3 (2004) + A1 (2012)
230/480V Series: Category C2
575V Series: Category C3
The drive can be modified for IT networks and corner grounding TN system
Electrostatic discharge Second environment, IEC 61000-4-2, 4 kV CD or 8 kV AD, Criterion B
Fast transient burst Second environment, IEC 61000-4-4, 2 kV/5 kHz, Criterion B
Dielectrical strength Primary to secondary:
 230 V: 4240 Vdc
 480 V: 5100 Vdc
 600 V: 5100 Vdc
Primary to earth:
 230 V: 2130 Vdc
 480 V: 2830 Vdc
 600 V: 3111 Vdc
Approvals CE, UL and cUL, EAC, RCM (C-Tick), RoHS (see nameplate for more detailed approvals)
Fieldbus connections Onboard DG1: EtherNet/IP, Modbus
®
TCP, Modbus RTU, BACnet
Onboard DH1: Modbus TCP, BACnet/IP, Modbus RTU, BACnet
Table 36. PowerXL Series, continued