10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.2 EtherCAT
PXR Electronic trip unit 01/21 MN012005EN www.eaton.com 111
10.2.3.2 Real-time data object register
Data that is subject to real-time changes, such as current, voltage and
energy, can be requested via sub index: 0 and indexes according to
→ table 65.
Real-time data can be obtained either in IEEE floating-point or fixed-point
format. For data displayed in fixed-point format, each result is presented as a
multiplication of the real-time data with a scaling factor. Energy objects can
only be obtained in fixed-point format.
Registers for which the IEEE floating-point value is not specified are only
supported in fixed-point format (FP).
Table 65: Real-time data register - EtherCAT
Index (Hex)
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit Scale
factor (FP)
2038 20B6 Cause of status:
High byte = primary status
Low byte = secondary status
– –
2039 20B7 I
L1
(IA) A 10
203A 20B8 I
L2
(IB) A 10
203B 20B9 IL3 (IC) A 10
203C 20BA I
G
(IG) A 10
203D 20BB I
N
( IN) A 10
203E 20BC U
L1-L2
(VAB) V 10
203F
20BD U
L2-L3
(VBC) V 10
2040
20BE U
L3-L1
(VCA) V 10
2041
20BF U
L1-N
(VAN) V 10
2042
20C0 U
L2-N
(VBN) V 10
2043
20C1 U
L3-N
(VCN) V 10
2048 20C6 Active 3-phase power W 1
2049 20C7 Reactive 3-phase power Var 1
204A 20C8 Apparent 3-phase power VA 1
204B
20C9 Power factor – 100
204C
20CA Frequency Hz 10
2051 20CF Peak active power demand W 1
2052 20D0 Product ID – –
2053 20D1 Frequency Hz 100
–
20D2 Active energy (forward) kWh 1
– 20D3 Active energy (reverse) kWh 1
– 20D4 Active energy combined (= forward + reverse) kWh 1
– 20D5 Apparent energy kVAh 1
–
20D6 Active energy (forward) Wh 1