INSTRUCTION MANUAL ECOSOFT RO SYSTEM
MO6500BWTSS
1.10 High feed pressure switch
This seng species if high feed pressure switch is normally closed (NC) or normally open (NO)
type.
1.11 Permeate backpressure switch
This seng species whether backpressure switch is normally closed (NC) or normally open (NO)
type.
1.12 Backpressure Standby delay
Specify the length of me before the controller goes into Standby if high permeate pressure
condion occurs (0…255 seconds). Controller will connue to operate in Service mode for the set
length of me before running pre-Standby forward ush or will iniate Forward ush immediately
if value set to 0.
1.13 Tank level switch
This seng species whether oat switch is normally closed (NC) or normally open (NO) type.
1.14 Tank level Standby delay
Specify the length of me before the controller goes into Standby if tank level switch goes high
(0…255 seconds). Controller will connue to operate in Service mode for the set length of me
before running pre-Standby forward ush or will iniate Forward ush immediately if value set to 0.
1.15 Display permeate TDS in ppm
If set to “on”, electrical conducvity (EC) of permeate will be displayed as TDS in ppm as TDS =
0.5147 * EC.
1.16 Permeate conducvity Fault threshold
Specify maximum acceptable permeate conducvity. Conducvity reading above this value will
iniate Fault mode (‘High permeate TDS’). If set to zero, fault threshold will not be used.
1.17 Permeate conducvity Fault delay
Specify the length of me before the controller goes into Fault mode when high permeate
conducvity is being read. Step 1.17 is displayed only if step 1.16 is set to non-zero value.
1.18 Display temperature
Select units of temperature (C for Celsius, F for Fahrenheit).
1.19 New sengs and calibraon passcode
Verify passcode.