EasyManua.ls Logo

Effekta MH6000 - Troubleshooting Common Issues

Effekta MH6000
51 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
UPS MH6000 Manual
MH Series
Page 41 of 51
Problem
Check the element
Solution:
The red LED at the UPS
glows up.
Check the failure code
which is indicated on
the LCD-display.
1. Er05 and
2. Er06, Er10, Er12, Er28
and
3. EPO
4. Er11
5. Er15
6. Er24
7. other failure code
1. Check if the connection of
the battery is correct, load
the batteries again for 8
hours to see if the UPS
backups normally.
2. Reduce the load at the
output of the UPS. If the
isolation of the cord is
damaged, it has to be
substituted.
3. Delete the short-circuit,
that has occurred on the
EPO-switch.
4. Remove items which
block the ventilated outputs.
5. Ensure that the UPS is in
normal service. If it is in
CVCF-mode, you have to
switch-off and start the UPS
again.
6. If the UPS is in CVCF-
mode, the bypass input is
blocked. You have to
switch-off the UPS and the
bypass input and then start
the UPS again.
7. Contact your local
supplier for help.
The autonomy time is
shorter than the nominal
value.
Load the batteries longer
that 8 hours and repeat the
test. If the problem still is
not solved, the batteries
have to be exchanged.
If your failure notice of the UPS is not mentioned in this schedule, please
contact our service department and keep this information ready:
1. model number, item number;
2. date of the day, when the problem occurred;
3. detailed description of the problem;

Related product manuals