UPS: MKD 700 3000 VA RT (XL) Technical Data
Housing dimensions 19” 2HE
(HxWxD in mm) incl. the respective
XL variants
86.5 x 438 x 435
86.5 x
438 x
604
Cooling
Fan cooling, convective;
Standards / Guidelines
Safety: EN 62040-1
EMV: EN 62040-2
Service: EN 62040-3
Environment
Temperature ranges
Operation: 0 … 40 °C
Recommended: + 15 … + 25 °C
exceeding the recommended range reduces
the battery life)
Storage: -25 ... 55 °C (without battery
bank!)
Influence of the operation altitude
< 1000 m MSL nominal power
> 1000 m MSL -> Verlust: ca. 1 % pro 100 m
Humidity
0 95 % non-condensing
Operation noise level
< 52 dB
13.1 Typical autonomous times
MKD:
700
1000
1500
2000
3000
UPS autonomous times:
Load 50 %
ca. 16 Min.
ca. 15 Min.
ca. 12 Min.
ca. 10 Min.
ca. 10 Min.
Load 100 %
ca. 6 Min.
ca. 5 Min.
ca. 4 Min.
ca. 4 Min.
ca. 4 Min.
XL Variants
Depending on the mounting and number of battery banks
13.2 Load-bearing capacity of the internal interface (DRY
CONTACT)
Connection:
Load-bearing capacity:
Voltage
Current:
Output (DRY-OUT):
30 VDC
60 VAC
2 A
1 A
Input (DRY-IN):
---
ca. 20 mA