UPS: MKD 700 3000 VA RT (XL) Initial Operation
7. Initial operation of the UPS
The initial operation generally requires that all previous chapters of this manual
have already been successfully read or processed. Additionally, check that all
connected loads are switched off.
The initial operation of UPS devices is exclusively reserved for accredited
personnel.
Please conduct the initial operation in the following order:
Switch on the mains power supply (circuit breaker) or connect the
UPS input to a wall socket;
The UPS automatically proceeds to the BY-PASS mode and also switches the
charging mode on. The loads are already being supplied.
In any case, it is possible to operate the device in the charging mode for a few
hours in order to conserve the complete charging status of the battery bank
before the UPS is started up and assumes its support function.
Check all the status information and parameters on the display;
Now start the device up; as a result, the USP switches to standard
mode (network mode);
Switch the loads on one at a time while observing the power values
displayed;
Briefly test the autonomous mode as well while observing the power
values and status information;
Now leave the UPS in standard mode (network mode); the loads are
fully secured by the UPS.
Follow the order in reverse to shut down the UPS.