Technical Data
AEROTOP T07RX-T10RX
45
Heat pump type AEROTOP T..RX T07RX T10RX
Heating operation For A2/W35
Heating Capacity Qh kW
6.4 9.1
Power input Pel kW
2 2.8
Performance number EN14511 COP -
3.3 3.3
Cooling operation for A35/W18
Cooling Capacity kW 6.7 9.7
Power input kW 2.6 3.7
Condenser Scroll hermetically
Maximum current consumption Imax A
17.3 23.5
Start-up current with smooth starter VSA A
40 40
Current intensity with blocked rotor LRA A
76 114
Current connection V-f-Hz
230-1-50
Fuse WP A/T
20 20
Fuse WP with electrical insert: 2 kW A/T
32 40
Fuse WP with electrical insert: 4 kW A/T
40 50
Fuse WP with electrical insert: 6 kW A/T
50 63
Condenser, heater side Material: Chrome steel AISI 304, 1.4301
Hydraulic connections IG R"
1” 1”
Water content incl. connection hoses AEROTOP T l
2.6 3
Volume stream heating operation nom/min
1
) l/h
1500/568 2100/835
Pressure loss heating operation kPa 28.3/4.4 32.9/4.1
Minimum volume stream cooling operation (t= 5 K) l/h
1'150 1'670
Pressure loss cooling operation kPa
17.4 16.1
Max working pressure
p baar
3 3
Evaporator/fan
Volume stream m
3
/h
2'500 3‘300
Available pressure
2)
Pa
150 92
Power consumption fan
3)
P kW
0.035 0.100
Maximum current consumption fan Imax A
1.6 1.6
Coolant -
R407C
Coolant filling AEROTOP TRX kg
5 7.5
Coolant circuit oil - Ester Oil
Oil quantity l 1.1 1.36
Weight heat pump kg 207 250
Sound Level
3)
Outdoor installation
Standard configuration
4)
Lwa dB(A)
62.0 65.3
Sound Level
3)
Indoor setup
Sound power level On suction Lwa dB(A)
53.0 56.0
On exhaust Lwa dB(A)
48.0
Inside Lwa dB(A)
50.0 54.0
53.0
1) Min: t max= 10 K, with PHW-preparation tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*t[K]*ρ[kg/l])*3600)
2) At maximum fan rotational speed.
3) Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the dis-
tance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine
the noise level see planning documents.
4) With Rain Guard