INSTALLATION MANUAL |
E CALCULATION TABLES FLUEGAS RESTRICTION
The calculation table shows when you need to place a ue gas ristrictor
This replace has no minimal starting length. the ue can start with a
bend directly from the top of the replace.
Result Action
V
No restrictor needed
O
Place the restrictor
X
No good operation guaranteed*
E�A HORIZONTAL TERMINAL FLUE DIAMETER 200/130 E�B VERTICAL TERMINAL FLUE DIAMETER 200/130
Total vertical Section
23
X X X X X X X X X X
22
V X X X X X X X X X
21
O O
V X X X X X X X
20
O O
V V X X X X X X
19
O O O O
V X X X X X
18
O O O O O
V V X X X
17
O O O O O O O
V V V
16
O O O O O O O O
V V
15
O O O O O O O O
V V
14
O O O O O O O O
V V
13
O O O O O O O O
V V
12
O O O O O O O O
V V
11
O O O O O O O O
V V
10
O O O O O O O O
V V
9
O O O O O O O O
V V
8
O O O O O O O O
V V
7
O O O O O
V V V V V
6
O O O O O
V V V V V
5
O O O O O
V V V V V
4
O O O O O
V V V V V
3.5
O O O O O
V V V V V
3
V V V V V V V V V V
2.5
V V V V V V V V V V
2
V V V V V V V V V V
1.5
V V V V V V V V V V
1
V V V V V V V V V X
0.5
V V V V V V V X X X
0
V V V V X X X X X X
0 0,5 1 2 2.5 3.5 4 4.5 5 6
Total Horizontal Section
Total vertical Section
10
O O O O O O O
V V V
9
O O O O O O O
V V V
8
O O O O O O O
V V V
7
O O O O O O O
V V V
6
O O O O O O O
V V V
5
O O O O O O O
V V V
4
O O O O O O O
V V V
3.5
O O O O O O O
V V V
3
V V V V V V V V V V
2.5
V V V V V V V V V V
2
V V V V V V V V V V
1.5
V V V V V V V V V V
1
V V V V V V V V V X
0.5
V V V V V V V X X X
0
V V V V X X X X X X
0 0.5 1 2 2.5 3.5 4 4.5 5 6
Total Horizontal Section
* Perhaps the powerfan is a good solution here.
Attention: For replaces is this ue category it is possible to reduce the
ue from a size 200/130 to a 150/100 ue, when the ue is exclusively
vertical.