EasyManua.ls Logo

Element4 SKY Series - Fire Safe Installation Procedures; Fire Safety Device Setup; Assembly Regulations

Default Icon
39 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8
Chapter 6
INSTALLATION MANUAL |
6 FIRE SAFE INSTALLATION
To install a gas replace as safely as possible, several installation
preparations need to be made. This overview can be used to assure the
re safety of a conversion of a replace.
6�1 FIRE SAFETY DEVICE SET-UP
Install the device such that there are no ammable materials around the
device or chimney. The device must never be placed against a back wall
of ammable materials.
Flammable materials, such as wood, can combust at a temperature of
85°C. At high temperatures this can happen within several minutes (over
200°C) or at lower temperatures (more than 85°C) this may occur over a
period of weeks.
A gas replace can achieve temperatures of over 200°C. Therefore one
should use only non-ammable materials around the replace and in
the cove.
It is important to follow the installation regulations below carefully. When
the regulations are insuciently- or not provided with the aspects of re
safety, the instructions according to NPR 3378-20:2010 are leading.
6�1�1 PROTECTION OF WALL AND CEILING
There are two kinds of walls/ceilings that can be distinguished,
respectively;
Type 1 is the non-combustible category. Walls/ceilings in this
group are made of mineral building materials (gas concrete,
bricks, lime sandstone etcetera.) of more than 10cm thickness.
For installations with these type of walls / ceiling please refer to CHAPTER CHAPTER
6.2.26.2.2 for more regulations.
Type 1 is the Combustibles category. Walls/ceilings that are made
of – or contain ammable building materials, and all walls on which
ammable objects (e.g. built-in furniture or wooden panels) are
mounted on the side of the wall that is turned away from the replace.
For these types of installations please refer to CHAPTER 6.2.3CHAPTER 6.2.3.
6�2 ASSEMBLY REGULATIONS
6�2�1 GENERAL ASSEMBLY REGULATIONS
Load-bearing walls and ceilings must be covered in a protective re
resistant plate.
Never use ammable materials around the replace or cove. The
minimal distance between the device and non-ammable materials
must be at 50 mm to ensure a convection air ow, also see section
14.3.4. The frames around the replace take into account this
distance.
Non-combustible materials may be installed to a zero clearance to
the outer faces of the appliance outer frame face, given they not
cover or prevent the removal of the glass panels or other parts of
the replace that need to be removed during maintenance.
The entire weight of the walls must be borne by a structure other
than the replace.
6�2�2 ASSEMBLY REGULATIONS FOR NON-FLAMMABLE MATERIALS
(Figure 6.1 | and Figure 6.2 |)
Make sure there is a good air ventilation in the cove. The
temperature that leaves through the ventilation grilles must not be
higher than 85°C. Therefore one should always make sure there are
enough ventilation grilles in the upper and lower parts of the cove.
6�2�3 ASSEMBLY REGULATIONS WITH FLAMMABLE MATERIALS
For reference see Figure 6.3 | and Figure 6.4 | on the next page.
Cover the walls/ceilings with a non-ammable, re resistant plate,
according to EN 13501-1:A2
Place a non-ammable, re resistant plate in front of the rst one at
a distance of 20mm or more.
Make sure that the two plates are not attached to each other by
screws or nails. Due to their conductivity these metals can cause a
heat bridge throught which a re may occur over time!

Table of Contents

Related product manuals