EasyManua.ls Logo

ELPRO 905U - Page 49

ELPRO 905U
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter Four Configuration
man_905-105_2.16 Page 49
Analog Sensitivity Configuration
The analog sensitivity is the change required in an analog input before a “Change Of State” is detected,
and the new analog value is
transmitted. For input signals which
vary widely over a short period of
time or have a normal oscillation,
the analog sensitivity should be set
to an appropriately large value. This
ensures that many change messages
are not transmitted in too short a
time. This will result in channel
congestion, as described in the
preceding section.
To change an analog sensitivity,
select “Sensitivities” on the left-
hand menu and double-click the
selected input. The sensitivity for
physical inputs is shown in mA and
internal input is shown as %.
SetPoint Configuration
Setpoints allow a remote
digital output to be turned
on and off depending on
the value of an analog
input. The “set-point
status” internal input must
be mapped to an output
for this option to have
effect. When the AI is
less than the Low Set-
point (LSP), the set-point
status will be active (on,
“1”) - when the AI is
more than the High Set
Point (HSP), the set-point
status will be reset (off,
“0”). Note that the High
Set Point (HSP) must always be higher than the Low Set Point (LSP). For the -1 module, only AI1 has
set-point values. For -2 modules, the first four analog inputs (AI 1 – 4) have set-points.
Debounce time operates on the set-point status in the same way as digital inputs.
To change a setpoint values, select “SetPoints” on the left-hand menu and double-click the selected
Setpoint Status.
Pulse Input Count Configuration

Table of Contents

Related product manuals