Installation Guide Flatpack2 -48V 150A ~ 2029242 R2, May 2008
5. Module Installation
CAUTION:
- Do not carry modules by the handles, even if they are warm
- Open the handles before inserting modules into shelves
Flatpack2 rectifiers incorporate an AC mains fuse in each line.
Double Pole / Neutral Fusing
Both the Smartpack controller and the Flatpack2 rectifier utilize the same locking
mechanism to keep the module fixed in place when installed into a system shelf.
Typically, the Smartpack controller is delivered installed in the system. If it is not
pre-installed, make required connection to the back of the controller before
installing (see Section 7).
To install modules:
1) Release the handles by inserting a small flat-blade screwdriver into the
release slots and pressing the tip upward; extend each handle.
2) Slide the module firmly into the shelf.
3) Latch the handles to lock the rectifier in place.
To remove modules:
1) Release the handles by inserting a small flat-blade screwdriver into the
release slots and pressing up.
2) Use the handles to pull the module out just far enough to where the body
can be held.
3) Slide the module out the rest of the way. Do not carry it by the handles.
Flatpack2 rectifiers weigh just over 4 lbs (1.9 kg) each.
Handle
Release