Symmetrix DMX-3 Specifications
Figure 64 on page 273 illustrates the North American (Delta) wiring
for Symmetrix DMX-3.
Figure 64 System bay and storage bay wiring, North America (Delta)
Customer
PDU B
Customer
PDU A
P
D
P
P
D
P
P
D
P
Storage
bay
P
D
P
50 A
circuit
breaker
50 A
circuit
breaker
50 A
circuit
breaker
Location Location
Location Location
8 AWG, Type W,
4-wire cable
8 AWG, Type W,
4-wire cable
Zone B
main input
200-240 VAC
three-phase
50-60 Hz
Delta
connection
Zone A
main input
200-240 VAC
three-phase
50-60 Hz
Delta
connection
B A
B A
System
bay
50 A
circuit
breaker
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
P
D
P
Storage
bay
(optional )
P
D
P
50 A
circuit
breaker
50 A
circuit
breaker
Location Location
B A
L1
L2
L3
L1
L2
L3
SYM-001214
Rear