1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 104/192
Digital output management:
Temperature differential to enable the freecooling function
Temperature differential for the free cooling regulation
Free cooling water pump OFF time if chiller only Free cooling
Free cooling water pump ON time if chiller only Free cooling
Free cooling maximum time
Proportional band Free coling
Minimum value Free cooling analog output
Maximum value Free cooling analog output
T1 probe selection for Free cooling
0=disabled, 1=Pb1, 2=Pb2, etc.
T2 probe selection for Free cooling
0=disabled, 1=Pb1, 2=Pb2, etc.
Outside temperature set point to force the maximum speed of
condenser fan
FC condensing fan maximum speed outside temperature differential
FC low temperature stop probe
FC low temperature stop set point
FC low temperature stop differential
Delay to enable compressors if temperature above set
FC analog out differential
Only free cooling for cooling (CF77=2)
Compressors are not used for cooling.
Evaporator and condenser water pumps are managed according to chiller probe and St01 set point; free
cooling valve/pump is managed according chiller probe and FS37 set point (or St01 if St01<FS37).
If the free cooling set point is not reached in FS36 minutes (0 = function disabled) or when the free
cooling set point is reached, the free cooling will be disabled for FS34 minutes.
After this time the valve/pump is switched on for FS35 seconds and, when this time is elapsed the
controller verify if T1 temperature – T2 temperature FS21 and if free cooling temperature > FS37.
If both condition are true, the free cooling valve/pump is activated.