Emerson Dixell iChill IC207D - FAN SPEED CONTROL IF COMPRESSORS AND FREE COOLING ARE USED FOR COOLING (CF77=3)

Emerson Dixell iChill IC207D
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 104/192
Digital output management:
Parameter
Description
min
max
udm
FS21
Temperature differential to enable the freecooling function
0
25.0
45
°C
°F
FS22
Temperature differential for the free cooling regulation
0.1
0
25.0
45
°C
°F
….
FS34
Free cooling water pump OFF time if chiller only Free cooling
0
250
min
FS35
Free cooling water pump ON time if chiller only Free cooling
0
250
sec
FS36
Free cooling maximum time
0
250
min
FS37
Set point Free cooling
-50.0
-58
0.0
0
70.0
158
50.0
725
°C
°F
bar
psi
FS38
Proportional band Free coling
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
FS39
Minimum value Free cooling analog output
0
100
%
FS40
Maximum value Free cooling analog output
0
100
%
FS41
T1 probe selection for Free cooling
0=disabled, 1=Pb1, 2=Pb2, etc.
0
10
FS42
T2 probe selection for Free cooling
0=disabled, 1=Pb1, 2=Pb2, etc.
0
10
FS43
Outside temperature set point to force the maximum speed of
condenser fan
0
1
FS44
FC condensing fan maximum speed outside temperature differential
0.1
0
25.0
45
°C
°F
FS45
FC condensing fan delay
0
250
min
FS62
FC low temperature stop probe
0
20
FS63
FC low temperature stop set point
-50.0
-58
110
230
°C
°F
FS64
FC low temperature stop differential
0.1
0
25.0
45
°C
°F
FS65
Delay to enable compressors if temperature above set
0
250
min
FS66
FC analog out differential
0.1
0
25.0
45
°C
°F
Only free cooling for cooling (CF77=2)
Compressors are not used for cooling.
Evaporator and condenser water pumps are managed according to chiller probe and St01 set point; free
cooling valve/pump is managed according chiller probe and FS37 set point (or St01 if St01<FS37).
If the free cooling set point is not reached in FS36 minutes (0 = function disabled) or when the free
cooling set point is reached, the free cooling will be disabled for FS34 minutes.
After this time the valve/pump is switched on for FS35 seconds and, when this time is elapsed the
controller verify if T1 temperature T2 temperature FS21 and if free cooling temperature > FS37.
If both condition are true, the free cooling valve/pump is activated.