1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 82/192
33. DYNAMIC SETPOINT
This function allows to modify the set point according to outside temperature or a 4..20mA analog input.
This function is enabled if:
In chiller mode the parameter Sd01 is not equal to 0.
In heat pump mode the parameter Sd02 is not equal to 0.
A analog input is configured as 4÷20mA for dynamic setpoint control or outside temperature
33.1 DYNAMIC SETPOINT DIAGRAM
Analog input configured as 4..20mA for dynamic setpoint:
Analog input configured as outside temperature and positive differential:
Analog input configured as outside temperature and negative differential: