1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 190/192
59. TECHNICAL SPECIFICATIONS
59.1 SUPPLY VOLTAGE
12Vac/dc -10% ÷ 15%, 50/60Hz, or
24Vac/dc -10% ÷ 10%, 50/60Hz
Molex connectors for power supply,
probes connection, digital inputs, analog
outputs)
STELVIO screw connectors for LAN
connection
STELVIO screw connectors for relay
59.2 ANALOGUE INPUTS
5 (NTC, PTC , D.I.)
3 (NTC, PTC, 4..20mA, 0..5V, D.I.)
Type of analogue input:
(configurable via software parameter)
NTC (-50T110°C; 10KΩ±1% a 25°C)
PTC (-50T150°C; 990Ω±1% a 25°C)
Rathiometric: 0.5..4.5V
Current: 4..20mA
Digital input (free contact)
-50°C ÷ 110°C (-58 °F ÷ 230°F) NTC
probe
-50°C ÷ 150°C (-58 °F ÷ 302°F) PTC
probe
0 bar ÷ 50 bar (0 psi ÷ 302 psi) pressure
probe
0.1 °C
1 °F
0.1 bar
1 psi
59.3 DIGITAL INPUT
Type:
(configurable via software parameter)
Free contact not opto-insulated
Don’t supply voltage to the digital inputs in
order to not cause damage to the
instrument
59.4 ANALOGUE OUTPUTS
Non opto-insulated, internal power
Type of analogue output:
(configurable via software parameter)
3 configurable outputs:
- OUT1: 0-10Vdc
- OUT2 and OUT 3:
0-10Vdc
4-20mA
PWM (to use with Dixell XV serie)
40mA (Out1..Out3) when connected to an