1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 73/192
When a water pump works continuosly for CO24 time, the other one is switched on and after CO25 second
the first one is switched off.
If a water pump overload occurs, the water pump is switched off and the other one is switched on.
27. CYCLIC OPERATION OF THE WATER PUMPS
If the water pump is OFF (reached set point), is possible to enable it to run to detect the right water
temperature.
At the end of the ON time, the controller verify if is necessary to switch on the compressor/s or not; if is not
necessary, the water pump is switched OFF for CO85 time and then switched on for another CO87 ON
cycle.
Evaporator water pump OFF time if the set point is reached
Evaporator water pump OFF time if the machine is STD-BY or
OFF
Evaporator water pump ON time
Condenser water pump OFF time if the set point is reached
Condenser water pump OFF time if the machine is STD-BY or
OFF
Condenser water pump ON time
28. HOT START
In the air air unit and in heating mode it is possible to stop the supply fan when the outlet evaporator
temperature falls below FA24 degrees.
FA24 Hot start Setpoint
FA25 Hot start differential
29. LOAD MAINTENANCE
It is possible to define for each load (compressors and water pumps) the number of working hours after witch
the display will show a maintenance warning.