1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 84/192
Auxiliary relay 1 winter minimum set point
Auxiliary relay 1 winter maximum set point
Auxiliary relay 1 winter set point
Auxiliary relay 1 summer differential
Auxiliary relay 1 winter differential
Auxiliary relay 2 operating mode
0= Not enabled
1= Always available with direct action
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
Analogue input configuration for auxiliary relay 2 control . Allows to select which probe
value Pb1..Pb10 controls the relay
Auxiliary relay 2 summer minimum set point
Auxiliary relay 2 summer maximum set point
Auxiliary relay 2 summer set point
Auxiliary relay 2 winter minimum set point
Auxiliary relay 2 winter maximum set point
Auxiliary relay 2 winter set point
Auxiliary relay 2 summer differential
Auxiliary relay 2 winter differential
Maximum operating time of auxiliary realys
AUX 1 relay operation mode
1= only in Chiller
2= only in Heat pump
3= in Chiller and Heat pump
AUX 2 relay operation mode
1= only in Chiller
2= only in Heat pump
3= in Chiller and Heat pump
35. AUXILIARY PROPORTIONAL OUTPUTS
The outputs OUT 3 .. OUT 6 can be configured as proportional output.
Each output is managed with a dedicated temperature or pressure probe; the parameters involved in the
probe selection are uS23 for the output 1 and uS35 for the output 2.
The function is enabled when the parameter uS22>0 for the output 1 and the parameter uS34>0 for the
output 2 and at least one output is configured as auxiliary output.
Par. uS22 configuration auxiliary output 1
Par. uS34 configuration auxiliary output 2
Value and function