1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 106/192
outside temperature > FS43 + FS44: condenser fan speed is forced at maximum speed
outside temperature < FS43: when outside temperature decreases below FS43 temperature, after FS45
minutes the condenser fan speed is managed as standard regulation
42. HEAT RECOVERY FUNCTION
The heat recovery function is enabled if:
1 Par. rC01 > 0
2 The unit is working in chiller mode
3 The condensing temperature or pressure is lower than set rC06 rC07
4 The heat recovery input/output resources are correctly configured
5 The heat recovery digital input is activated and or a heat recovery probe is configured
If the heat recovery is configured, in the menu the REC sub-menu is available to read the status of the
valves and to disable / enable the function.
42.1 HEAT RECOVERY TEMPERATURE PROBE
If single valve is configured:
If two valves are configured: