1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 81/192
MONDAY
X = 0 - Y= 0: energy saving and automatic on/off are both disabled
MONDAY
X = 0 - Y= 1: the energy saving is disabled, the automatic on is enabled in time band 1
MONDAY
X = 3 - Y= 7: the energy saving is enabled in time band 1 and time band 2, the automatic on is enabled in
time band 1, time band 2 and time band 3.
WEEKLY PROGRAMMING
Repeat the daily programming for the other days of the week using parameters ES08..ES13.
32.4 HOW TO SWITCH ON THE CONTROLLER WHEN IT IS OFF BY REAL TIME
CLOCK
When the unit is in OFF by RTC and the parameter ES18 > 0, if the user switch on the controller by
keyboard the unit stay on for ES18 time; when this time is elapsed the unit return to OFF.