Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL44
Automatic – It becomes manual after AL42 events/hour
Logged only if manuale
On the display the symbol is blinking
ATTENTION
If during AL44 the alarm stop and start again the AL44 time delay is reloaded.
ALC2: Generic Signal alarm
Label on alarm
visualization menu
ALC1: generic signal alarm from digital input if AL50 = 0
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL52
Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL53
On the display the symbol is blinking
ATTENTION
If during AL53 the alarm stop and start again the AL44 time delay is reloaded.
ALC2: Generic alarm with stop regulation
Label on alarm
visualization menu
ALC1: generic signal alarm from digital input with stop regulation if AL50 = 1
Digital input configured as generic alarm with stop regulation active after the
delay in Par. AL52
Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL53
Automatic – It becomes manual after AL51 events/hour
Logged only if manuale
On the display the symbol is blinking
ATTENTION
If during AL53 the alarm stop and start again the AL44 time delay is reloaded.
ALSF: Phase sequence alarm
Label on alarm
visualization menu