EasyManua.ls Logo

Emerson Dixell iChill IC207D - CIRCUIT ALARM

Emerson Dixell iChill IC207D
192 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 132/192
47.2 CIRCUIT ALARM
Alarm
Code
Alarm description
Compressors
of the circuit
(n)
Compressors
of the other
circuit
Fan condensing of
the circuit (n)
Fan condensing
of the other
circuit
b(n)AC
Anti-freeze in chiller of the circuit (n)
OFF
OFF
b(n)Ac
Anti-freeze circuit (n) message in chiller
b(n)AH
Anti-freeze in heat pump of the circuit (n)
OFF
OFF
b(n)Ah
Anti-freeze circuit (n) message in heat pump
b(n)Cu
Unloading from condenser high temp/press of the circuit (n)
b(n)Cu
Unloading from evaporator low temp/press of the circuit (n)
OFF
OFF
b(n)dF
Bad defrost circuit (n)
b(n)ds
Circuit (n) disabled from keyboard
OFF
OFF
b(n)HP
High pressure switch of the circuit (n)
OFF
OFF after 60 seconds
b(n)hP
High condensing pressure of the circuit (n)
OFF
OFF after 60 seconds
b(n)hP
High condensing temperature from NTC of the circuit (n)
OFF
OFF after 60 seconds
b(n)LP
Low pressure switch of the circuit (n)
OFF
OFF
b(n)LP
Low condensing pressure - (evaporating with low pressure transducer)
with transducer of the circuit of the (n)
OFF
OFF
b(n)lP
Low condensing temperature NTC circuit (n)
OFF
OFF
b(n)PH
Pump down alarm in stop regulation of the circuit (n)
OFF
OFF
b(n)PL
Pump down in regulation start-up of the circuit (n)
OFF
OFF
b(n)rC
Recovery function disabled in circuit (n)
b(n)tF
Fan overload circuit (n)
OFF
OFF
b(n)UA
Expansion valve 1 or valve 2 alarm (n)
OFF
OFF
(n) identifies the circuit 1 or 2