1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 143/192
66. By-pass gas valve compressor 2
67. Direct start: compressor 3 relay
PW start: relay PW 1 of the compressor3
68. PW start: relay PW 2 of the compressor 3
69. Capacity step valve 1 compressor 3
70. Capacity step valve 2 compressor 3
71. Capacity step valve 3 compressor 3
72. By-pass gas valve compressor 3
73. Direct start: compressor 4 relay
PW start: PW 1 of the compressor 4
74. PW start: relay PW 2 of the compressor 4
75. Capacity step valve 1 of the compressor 4
76. Capacity step valve 2 of the compressor 4
77. Capacity step valve 3 of the compressor 4
78. By-pass gas valve compressor 4
79. Compressor 5
80. Compressor 6
49.5 ANALOG OUTPUT OUT1 (0 10 VOLT / 4..20MA)
0 Not enabled
1 Modulated evaporator water pump
2 Modulated Free cooling valve
3 not used
4 Auxiliary output 10V 1
5 Auxiliary output 10V 2
6 Proportional output for modulating compressor 1
7 Proportional output for modulating compressor 2
8 Condenser fan circuit 1
9 Condenser fan circuit 2
After selection number 9 it is possible to configure the analog output as digital output with the same meaning
of the relays configuration; every analog output can be configured from o 1” to c54 (see relay
configuration table).
49.6 ANALOG OUTPUT OUT2 E OUT3 (0 10 VOLT / 4..20MA / PWM)
0 Not enabled
1 Modulated evaporator water pump (0..10 Vdc)
2 Modulated Free cooling valve (0..10 Vdc)
3 not used
4 Auxiliary output 10V 1 (0..10 Vdc)
5 Auxiliary output 10V 2 (0..10 Vdc)
6 Proportional output for modulating compressor 1 (0..10 Vdc)
7 Proportional output for modulating compressor 2 (0..10 Vdc)
8 Condenser fan circuit 1 (0..10 Vdc)
9 Condenser fan circuit 2 (0..10 Vdc)
10 Condenser fan circuit 1 (PWM)
11 Condenser fan circuit 2 (PWM)
After selection number 11 it is possible to configure the analog output as digital output with the same
meaning of the relays configuration; every analog output can be configured from o 1” to c54 (see relay
configuration table).
49.7 OTHER OUTPUTS
o LAN to connect I/O Expansion module (IPX207D model)