1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 150/192
Sd 15
Summer outside temperature analog 2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 16
Winter outside temperature analog 2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 17
Summer outside temp. differential analog 2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 18
Winter outside temp. differential analog 2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 19
Dynamic set point: summer offset relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 20
Dynamic set point: winter offset relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 21
Summer outside temperature relay AUX1
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 22
Winter outside temperature relay AUX1
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 23
Summer temperature differential relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 24
Winter temperature differential relay AUX1
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 25
Dynamic set point: summer offset relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 26
Dynamic set point: winter offset relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 27
Summer outside temperature relay AUX2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 28
Winter outside temperature relay AUX2
-50.0
-58
110.0
230
°C
°F
Dec
int
Sd 29
Summer temperature differential relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Sd 30
Winter temperature differential relay AUX2
-30.0
-54
30.0
54
°C
°F
Dec
int
Parameter
Description
min
max
M. u.
Resolution
ES 1
Start of the Time band 1 (0÷24)
0
24.00
Hr
10 Min
ES 2
End of the Time Band 1 (0÷24)
0
24.00
Hr
10 Min
ES 3
Start of the Time band 2 (0÷24)
0
24.00
Hr
10 Min
ES 4
End of the Time Band 2 (0÷24)
0
24.00
Hr
10 Min
ES 5
Start of the Time band 3 (0÷24)
0
24.00
Hr
10 Min
ES 6
End of the Time Band 3 (0÷24)
0
24.00
Hr
10 Min
ES 7
Monday: energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 8
Tuesday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 9
Wednesday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 10
Thursday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 11
Friday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 12
Saturday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 13
Sunday energy saving activated
Automatic unit on-off
0 - 0
7 - 7
ES 14
Energy Saving setpoint offset in chiller mode
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 15
Energy Saving differential in chiller mode
0.1
0
25.0
45
°C
°F
Dec
int
ES 16
Energy Saving setpoint offset in heat pump mode
-30.0
-54
30.0
54
°C
°F
Dec
int
ES 17
Energy Saving differential in heat pump mode
0.1
0
25.0
45
°C
°F
Dec
int
ES 18
Maximum ON time when the unit is switched on by keyboard starting from
OFF state by RTC
0= Not enabled
1
250
10 min
min
ES 19
Start of the Time band 1 Domestic hot water (0÷24)
0
24.00
Hr
10 Min
ES 20
End of the Time band 1 Domestic hot water (0÷24)
0
24.00
Hr
10 Min
ES 21
Start of the Time band 2 Domestic hot water (0÷24)
0
24.00
Hr
10 Min
ES 22
End of the Time band 2 Domestic hot water (0÷24)
0
24.00
Hr
10 Min
ES 23
Start of the Time band 3 Domestic hot water (0÷24)
0
24.00
Hr
10 Min
ES 24
End of the Time band 3 Domestic hot water (0÷24)
0
24.00
Hr
10 Min
ES 25
Monday: Domestic hot water 2
nd
set point activation
0
7
ES 26
Tuesday: Domestic hot water 2
nd
set point activation
0
7
ES 27
Wednesday: Domestic hot water 2
nd
set point activation
0
7
ES 28
Thursday: Domestic hot water 2
nd
set point activation
0
7