1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 152/192
Operative mode of the evaporator pump / supply fan (See Evaporator pump
function)
0= Not enabled (evaporator pump or supply fan).
1= Continuous. When the unit is running in Chiller or HP the pump or the
supply fan is running.
2= With compressor. When a compressor is running also the pump or the
supply fan is running.
ON compressor delay after water pump / supply fan start-up (See water pump
functioning).
OFF delay evaporator water pump / supply fan after compressor switching
OFF. This delay is also active when the unit is turned in stand-by (See
evaporator water pump function).
Number of time running hours for pump rotation (See water pump group
function)
Time to make run the pumps together before rotating from one to the other
(See water pump group function)
Operative mode for condenser water pump (See condenser water pump
function)
0= Not enabled.
1= Continuous. When the unit is running in Chiller or HP the is running.
2= With compressor. When a compressor is running also the pump is running.
OFF delay condenser water pump after compressor switching OFF. This
delay is also active when the unit is turned in stand-by (See evaporator water
pump function).
Number of time running hours for pump rotation (See water pump group
function).
Time to make run the pumps together before rotating from one to the other
(See water pump group function).
Compressor 1 operation time to generate maintenance warning
Compressor 2 operation time to generate maintenance warning
Compressor 3 operation time to generate maintenance warning
Compressor 4 operation time to generate maintenance warning
Compressor 5 operation time to generate maintenance warning
Compressor 6 operation time to generate maintenance warning
“Evaporator pump / Supply fan” operation time to generate maintenance
warning
2nd Evaporator pump operation time to generate maintenance warning
Condenser pump operation time to generate maintenance warning
2nd Condenser pump operation time to generate maintenance warning
Pump down operating mode (See pump down ON/OFF function)
0= Not enabled
1= Unit off with pump–down, unit on without pump–down
2= Unit off with pump–down, unit on with pump–down
3= Chiller mode off with pump–down, chiller mode on without pump–down
4= Chiller mode off with pump–down, chiller mode on with pump–down
Pump–down pressure setpoint (See pump down ON/OFF function)
Pump-down pressure differential (See pump down ON/OFF function)
Maximum pump–down time duration at start-up and stop (See pump down
ON/OFF function)
Unloading compressor setpoint in chiller. From high temperature of the
evaporator water inlet (See unloading function).
Unloading Differential. From high temperature of the evaporator water inlet
(See unloading function).
Delay time to engage the Unloading function from high temperature of the
evaporator water inlet (See unloading function).
Maximum unloading duration time to keep activated the Unloading function
from high temperature of the evaporator water inlet (See unloading function).
Unloading compressor setpoint. From temperature / pressure in chiller mode
(See unloading function).
Unloading Differential. From temperature / pressure in chiller mode (See
unloading function).
Unloading compressor setpoint. From temperature / pressure in HP mode
(See unloading function).